Generic
Modbus RTU Sensor
What You Need
Customer provides:
- Sensor register map / datasheet
- RS-485 wiring path
- Sensor power supply
Physical Connection
- 1
Identify RS-485 terminals
Locate the RS-485 A (+), B (-), and GND terminals on the sensor. These are typically screw terminals labeled A/B or D+/D-.
- 2
Wire RS-485 bus
Connect shielded twisted pair cable from the sensor to a USB-to-RS485 adapter on the Flowstate edge node. Use daisy-chain topology for multiple sensors.
Add 120 ohm termination resistors at both ends of the bus. Maximum bus length: 1200m (4000ft).
- 3
Power the sensor
Provide power per the sensor's spec (commonly 12-24V DC). Use the same power supply ground as the RS-485 bus ground.
Machine Configuration
- 1
Set Modbus address
Set a unique Modbus station address (1-247) on the sensor via DIP switches, buttons, or configuration software. Note the baud rate and parity settings.
- 2
Configure register map
Obtain the sensor's Modbus register map from the manufacturer. Note register addresses, data types (INT16, FLOAT32), and byte order (big/little endian).
- 3
Create Flowstate template
In the Flowstate edge node, create a Modbus RTU device template with the sensor's register map. Map registers to named metrics.
Verification
- 1
Read test registers
Use modpoll or the Flowstate diagnostics tool to read a known register. Verify the value matches the sensor's display.
- 2
Dashboard check
Sensor metrics appear in Flowstate with correct units and scaling.
Available Metrics (4)
Don't have Modbus RTU access?
The universal CT clamp works on any machine — 15 minutes, zero configuration.
CT Clamp Fallback GuideReady to Connect?
Calculate what downtime is costing you, then get started.