Grundfos
CIM 500
Also applies to: CIM 250, CIM 500 Modbus
What You Need
Customer provides:
- CIM 500 module (or we can procure)
- Network access
Physical Connection
- 1
Install CIM 500 module
Slide the CIM 500 communication module into the Grundfos pump controller's CIM slot. The module clicks into place.
CIM 500 is compatible with Grundfos E-pumps, CR, CRE, TP/TPE, NB/NBE, and other series with a CIM slot.
- 2
Connect Ethernet
Connect a Cat6 cable from the CIM 500 RJ45 port to the Flowstate edge node.
- 3
Set IP address
Use Grundfos GO Remote app or the pump controller display to set a static IP in the 10.0.100.x range.
Machine Configuration
- 1
Enable Modbus TCP
Via the pump controller or GO Remote app: Communication > Protocol > Modbus TCP. Set Unit ID (default 1).
- 2
Configure register map
CIM 500 exposes standard Grundfos registers. Flow rate (register 200), pressure (202), power (206), runtime hours (210).
Verification
- 1
Test Modbus connection
From the edge node, read register 200 using modpoll or the Flowstate diagnostics tool. Verify flow rate reading.
- 2
Dashboard check
Pump appears in Flowstate within 60 seconds with flow, pressure, and power metrics.