Siemens

SINAMICS G120

Also applies to: G120C, G120D, G120P, G120X

60 minutesAdvancedPROFINET

What You Need

Cat6 Ethernet cableIncluded in kit
Flowstate CL260 edge nodeIncluded in kit
USB-to-RS485 adapter (Modbus RTU fallback only)

Customer provides:

  • Network access
  • Drive parameter access (password if set)

Physical Connection

  1. 1

    Locate PROFINET port

    The G120 Control Unit (CU) has an RJ45 PROFINET port on the front. G120C models have a built-in 2-port switch.

  2. 2

    Connect Ethernet

    Cat6 from the CU PROFINET port to the Flowstate edge node.

  3. 3

    Set IP address

    Use Siemens STARTER or BOP-2 panel: P0918 (IP byte 1), P0919 (byte 2), P0920 (byte 3), P0921 (byte 4).

    For Modbus RTU fallback: connect RS-485 (terminals 14/15 on CU) to a USB-to-RS485 adapter on the edge node.

Machine Configuration

  1. 1

    Enable PROFINET

    Set P2030 = 1 (PROFINET mode). Set device name via STARTER or DCP discovery.

  2. 2

    Configure process data

    Standard telegram 1 provides speed setpoint/actual, current, status word. Set P0922 for telegram type.

Verification

  1. 1

    DCP discovery

    Run a PROFINET DCP scan from the edge node. The G120 should appear with its configured device name.

  2. 2

    Verify data

    Flowstate dashboard shows frequency, current, motor temperature, and fault codes.

Available Metrics (8)

Output frequency (Hz)
Output current (A)
Motor temperature (C)
DC bus voltage (V)
Drive status (run/stop/fault)
Fault code
Power consumption (kW)
Runtime hours